4.10
Question
Suppose that heat leaks into your kitchen refrigerator at an average rate of 300 watts. Assuming ideal operation, how much power must it draw from the wall?
Step-by-Step Solution
Verified Answer
The power drawn from wall is 57.69 W.
1Step 1 : Given information
Assume temperatures T1 = 250 K and T2 = 298 K
Power leak = 300 W
2Step 2 : Explanation
COP can be found by using
Substitute the values
The amount of power drawn from the wall is: